How Many Solar Panels Does It Take to Run a Swamp Cooler?

Panel watts for 1/3, 1/2 and 3/4 hp swamp coolers, Breezair and Portacool models at 6 and 10 hours a day, sized to August sun in nine Western cities, plus the inverter surge each motor needs.

Short answer

About 1,000 W of panels, five 200 W panels, runs a 1/3 hp swamp cooler six hours a day in Phoenix in August. A 1/2 hp cooler needs about 1,430 W (eight panels) and a 3/4 hp cooler about 1,720 W (nine). Ten hours a day takes two thirds more. The inverter matters as much as the panels: it has to deliver the motor's locked-rotor surge, about 2,000 W for 1/3 hp and 3,000 W for 1/2 hp.

Key takeaways

  • A whole-house cooler draws about 740 W (1/3 hp), 1,090 W (1/2 hp) or 1,310 W (3/4 hp) on high with its pump, so six hours a day is 4.4 to 7.9 kWh.
  • Each watt of panel delivers about 4.6 Wh a day to the cooler in Phoenix in August: 6.91 kWh/m2/day of sun from NASA POWER times a 0.66 derate for system losses, hot cells and the inverter.
  • August is the design month: it has the least sun of June, July and August in all nine cities checked, from 6.31 kWh/m2/day in Denver to 7.42 in Fresno.
  • Hunker's "200 W panel and 200 W inverter" is sized for a 1.4 A, 161 W cooler. A 1/3 hp cooler runs at 740 W and needs about 2,000 W of surge to start; a 250 VA inverter peaks at 400 W.
  • Running on low speed cuts the panel count by about a quarter: a 1/3 hp Nidec motor drops from 5.5 to 3.9 A.
On this page
  1. Solar panels needed by cooler motor
  2. How the panel watts are worked out
  3. Sun by city: why August sets the size
  4. Breezair and portable coolers
  5. The inverter has to start the motor
  6. The "200 W panel and 200 W inverter" answer
  7. Ways to need fewer panels
  8. Where these numbers stop applying
  9. Frequently asked questions

About 1,000 W of solar panels, five 200 W panels, runs a 1/3 hp swamp cooler six hours a day in Phoenix in August. A 1/2 hp cooler needs about 1,430 W, eight panels, and a 3/4 hp cooler about 1,720 W, nine panels. Running ten hours a day takes two thirds more. The panels are only half the job: the inverter has to deliver the motor's starting surge, about 2,000 W for 1/3 hp and 3,000 W for 1/2 hp, and that is where most small solar setups fail.

Below are the loads, the sun in nine Western cities, the losses between the panel and the motor, and the inverter each motor size needs. The starting-current numbers are the same ones that size a backup generator in what size generator for a swamp cooler.

Solar panels needed by cooler motor

Each row is sized to August in Phoenix, the cloudiest of the three summer months there, with the cooler on high speed while the sun is up.

Panel watts to run a whole-house swamp cooler in Phoenix in August (blower on high plus a 0.7 A pump, 0.66 derate)
MotorRunning loadEnergy, 6 h / 10 hPanel watts, 6 hPanel watts, 10 hInverter surge needed
1/3 hp, 115 V740 W4.4 / 7.4 kWh970 W (5 x 200 W)1,620 W (9 x 200 W)About 2,000 W
1/2 hp, 115 V1,090 W6.5 / 10.9 kWh1,430 W (8 x 200 W)2,380 W (12 x 200 W)About 3,000 W
3/4 hp, 115 V1,310 W7.9 / 13.1 kWh1,720 W (9 x 200 W)2,860 W (15 x 200 W)About 4,600 W

Running loads come from real motor nameplates on high speed: 5.5 A for a Nidec 6767 (1/3 hp), 8.4 A for a Century SVB2054V1 (1/2 hp) and 10.2 A for a Nidec 6770 (3/4 hp), each plus the 0.7 A Champion pump, times 120 V. Which motor your cooler has depends on the cabinet; what size motor for a swamp cooler lists them by model.

How the panel watts are worked out

Three numbers decide it: how much energy the cooler uses in a day, how much sun falls on the panel, and how much of the panel's rating survives the trip to the motor.

Panel watts = (running watts x hours a day) / (sun hours x 0.66)

Sun hours are NASA's figure for the month in kWh per square meter per day. A panel's rating assumes 1,000 W per square meter, so each kWh/m2 is one hour of full sun. The 0.66 is the derate, and it is built from four parts:

The 0.66 derate, from panel to cooler
LossFactorWhere it comes from
System losses0.86The 14% total in the California Energy Commission's PV derating table: soiling 2%, wiring 2%, connections 0.5%, light-induced degradation 1.5%, nameplate rating 1%, age 5%, availability 3%. The CEC models its table on the single derating factor PVWatts uses.
Hot cells0.86Renogy's 200 W panel loses 0.37% of its power per degree C above 25 C and has a NOCT of 47 C, which PVEducation defines at 800 W/m2 and 20 C air. That is 27 C above the air, so on a 35 C (95 F) day the cells run near 62 C: 37 degrees over, a 13.7% loss.
Charge controller0.98Victron's SmartSolar MPPT: "Maximum efficiency exceeds 98 %."
Inverter0.91Victron's Phoenix 12/1200: 91% maximum efficiency at 12 V.

Multiplied together, a panel delivers about two thirds of its rating to the cooler. The controller and inverter figures are maximum efficiencies, so a real system does no better.

Worked example: 1/3 hp cooler, six hours a day, Phoenix in August

Energy: 740 W x 6 h = 4,440 Wh. Sun: 6.91 kWh/m2/day. Each watt of panel delivers 6.91 x 0.66 = 4.56 Wh a day. Panel: 4,440 / 4.56 = 974 W, five 200 W panels.

Sun by city: why August sets the size

NASA's POWER project publishes a 25 year climatology, 2001 to 2025, of the sunlight reaching the ground in every month. In all nine cities below, August has the least sun of the three summer months, so a system sized for August covers the whole cooling season.

Sun (kWh/m2/day, NASA POWER 2001 to 2025) and panel watts for six hours a day, sized to August
CityJuneJulyAugustYear1/3 hp1/2 hp3/4 hp
Fresno8.468.117.425.44900 W1,330 W1,600 W
Las Vegas8.527.567.085.61950 W1,400 W1,680 W
Phoenix8.507.496.915.85970 W1,430 W1,720 W
El Paso8.137.286.795.90990 W1,460 W1,750 W
Boise7.547.746.674.561,010 W1,480 W1,780 W
Albuquerque8.107.216.645.531,010 W1,490 W1,790 W
Salt Lake City7.817.536.594.801,020 W1,500 W1,800 W
Tucson8.326.916.515.791,030 W1,520 W1,820 W
Denver7.227.006.314.851,060 W1,570 W1,880 W

For ten hours a day, multiply by 10/6: a 1/2 hp cooler in Denver goes from 1,570 to 2,610 W. Tucson and Phoenix lose the most sun between June and August, about 22% and 19%. Those are also the months when monsoon humidity cuts the cooling itself, as explained in swamp coolers during monsoon season. Whether a cooler is worth running at all in a given city is a separate question, answered by the swamp cooler climate index.

Breezair and portable coolers

Seeley International publishes a total "Power Max" for each Breezair, which includes the pump, and Portacool lists running amps. Seeley's figure is a maximum, and Portacool lists one current per model.

Panel watts for Breezair and Portacool coolers in Phoenix in August (at listed maximum power)
CoolerListed powerEnergy, 6 hPanel watts, 6 hPanel watts, 10 h
Portacool Jetstream 220 (2,400 CFM)3.4 A, about 410 W2.4 kWh540 W890 W
Portacool Jetstream 250 (8,500 CFM)6.6 A, about 790 W4.8 kWh1,040 W1,730 W
Breezair EXT 155 (115 V)930 W5.6 kWh1,220 W2,030 W
Breezair EXT 265 (115 V)990 W5.9 kWh1,300 W2,160 W
Portacool Jetstream 230 (3,600 CFM)8.3 A, about 1,000 W6.0 kWh1,310 W2,180 W
Portacool Jetstream 260 (12,500 CFM)9.3 A, about 1,120 W6.7 kWh1,460 W2,440 W
Breezair EXQ 170 (240 V)1,220 W7.3 kWh1,600 W2,670 W
Portacool Jetstream 270 (22,500 CFM)15.2 A, about 1,820 W10.9 kWh2,390 W3,990 W
Breezair EXQ 210 (240 V)1,870 W11.2 kWh2,450 W4,090 W

The Jetstream 230 draws more than the 250 despite moving less than half the air, so on solar it is the worse buy; the portable evaporative cooler buying guide covers the other trade-offs. The EXQ models need a 240 V inverter. For what else separates a Breezair from a belt-drive cooler, see the Breezair guide.

The inverter has to start the motor

A belt-drive cooler motor draws its locked-rotor current for the moment before the shaft turns. Generac's motor table lists 25 A for a 1/2 hp motor and 38 A for 3/4 hp at 120 V, 50 A per horsepower, which puts a 1/3 hp motor near 17 A. At 120 V that is about 2,000, 3,000 and 4,600 W of surge, before the pump.

Victron's Phoenix datasheet shows how that sorts the inverters:

Victron Phoenix inverters against a 1/3 hp cooler (740 W running, about 2,000 W to start)
ModelContinuous at 25 C / 40 CPeak1/3 hp cooler
12/250200 / 175 W400 WCannot run or start it
12/800650 / 560 W1,500 WCannot run or start it
12/12001,000 / 850 W2,200 WRuns it; starts it with about 100 W to spare
12/16001,450 / 1,200 W2,200 WRuns it; same peak as the 1200

A 1/2 hp cooler's 1,090 W running load exceeds the 12/1200's continuous rating, and its 3,000 W start is beyond the 2,200 W peak of every model in the line, so it needs a larger inverter rated for at least 3,000 W of surge. Victron also derates these inverters 1.25% per degree C above 40 C, so mount the inverter out of the attic and out of the sun. The same motor numbers set the permanent circuit in swamp cooler breaker and wire size.

The "200 W panel and 200 W inverter" answer

The most quoted answer to this question is Hunker's: a 200 W panel, one 100 Ah battery and a 200 W inverter. The arithmetic is right for the cooler it uses, a label reading 1.4 A, which Hunker works out to 161 W and 966 Wh for six hours. The problem is the cooler. A 1/3 hp rooftop unit runs at 740 W, 4.6 times that, and the smallest portable on Portacool's Jetstream sheet draws 3.4 A.

The inverter advice is where the answer breaks for a real cooler. Hunker says a 200 W inverter "should work fine" because it is rated above the running power. A 1/3 hp cooler needs 740 W to run and about 2,000 W to start; Victron's 250 VA model delivers 200 W continuous and 400 W peak. It will not start the motor, and even a running motor would overload it nearly fourfold.

Hunker's panel figure also leaves out losses. It takes "five to six peak hours of sunshine a day" and counts the full 200 W, for 1.0 to 1.2 kWh. Phoenix's August sun of 6.91 is above that range, but after the 0.66 derate a 200 W panel delivers about 910 Wh, short of even its own 966 Wh target. Sized properly, the 1/3 hp cooler needs the five panels in the first table, not one.

Ways to need fewer panels

  • Run on low speed. The Nidec 6767 draws 3.9 A on low against 5.5 A on high. With the pump that is 550 W instead of 740 W, about a quarter fewer panels: 720 W for six hours in Phoenix in August. Two-speed motor wiring explains the speed leads.
  • Run the hours the sun is up. Every figure here assumes that. A battery that carries the cooler into the evening adds charge and discharge losses on top of the 0.66.
  • Go 12 V for one room. A purpose-built DC cooler draws 26 to 55 W, as the 12 volt swamp cooler for an RV or van shows, and a single 100 to 200 W panel covers it. A home-built one is in DIY swamp cooler.

On a grid-tied home the question is different: panels offset the cooler's kWh on the bill, with no inverter surge to plan for. Swamp cooler operating cost has those numbers.

Where these numbers stop applying

  • Sun is measured on flat ground. NASA's figure is global horizontal irradiance, sunlight on a horizontal plane. Tilt, orientation and shade change what a panel collects, and a panel in shade for part of the day needs a site-specific estimate.
  • Averages hide bad weeks. August's 6.91 in Phoenix is a 25 year average. A run of cloudy monsoon days delivers less, and the cooler slows or stops unless the battery has reserve.
  • The heat loss assumes a 35 C (95 F) day. Hotter air or a roof-mounted panel with little airflow behind it runs hotter cells, and every extra degree C costs 0.37%.
  • Locked-rotor figures are general. Generac's table covers single-phase motors by horsepower, not cooler motors specifically. A nameplate locked-rotor figure, where present, overrides it. A motor that already struggles to start on the grid will not start on an inverter; see swamp cooler motor not running.

Frequently asked questions

Can a 100 W solar panel run a swamp cooler?

Not a rooftop or large portable cooler. A 100 W panel delivers about 460 Wh a day to the load in Phoenix in August after losses, enough for a 1/3 hp cooler for about 37 minutes. It can run a small 12 V cooler drawing 26 to 55 W for most of a day.

How many solar panels do I need for a 1/2 hp swamp cooler?

About 1,430 W of panels for six hours a day in Phoenix in August, which is eight 200 W panels, and about 2,380 W (twelve panels) for ten hours. Denver needs about 10% more panel than Phoenix. The inverter also has to supply about 25 A at 120 V, roughly 3,000 W, to start the motor.

What size inverter does a swamp cooler need?

Size it to the starting surge, not the running watts. Generac's motor table puts locked-rotor current at 25 A for 1/2 hp and 38 A for 3/4 hp at 120 V, and 50 A per horsepower works out to about 17 A for 1/3 hp. That is about 2,000, 3,000 and 4,600 W of surge. A 1,200 VA inverter with a 2,200 W peak suits a 1/3 hp cooler and nothing larger.

Can I run a swamp cooler directly off a solar panel without a battery?

Only a DC cooler, with a DC fan and pump wired to the panel, and it slows or stops when a cloud passes. A 120 V AC cooler needs an inverter, and an inverter needs a battery to supply the starting surge and keep the voltage steady.

Do I need more panels to run the cooler at night?

Yes. The figures here assume the cooler runs while the sun is up. Energy stored in a battery and used after sunset passes through charging and discharging losses that are not in the 0.66 derate, so each evening hour needs more panel than a daytime hour.

Sources and further reading

  1. POWER Climatology API, ALLSKY_SFC_SW_DWN (all sky surface shortwave downward irradiance), 2001 to 2025, point queries for nine cities, NASA Langley Research Center, POWER Project
  2. Appendix C: Photovoltaics, 2025 Building Energy Efficiency Standards (Table C-1, Derating Factor), California Energy Commission
  3. RSP200D 200W Monocrystalline Solar Panel datasheet, Renogy
  4. Nominal Operating Cell Temperature, PVEducation
  5. Phoenix Inverter VE.Direct 250VA to 1600VA datasheet, Victron Energy
  6. SmartSolar charge controller MPPT 100/30 and 100/50 datasheet, Victron Energy
  7. Generator Sizing Guide (Table 1 and sizing worksheet), Generac Power Systems, hosted by Home Power Systems
  8. Nidec 6767, 1/3 hp 2-speed 115 V evaporative cooler motor, Electric Motor Warehouse
  9. Century SVB2054V1, 1/2 hp 2-speed 115 V evaporative cooler motor, Electric Motor Warehouse
  10. Nidec 6770, 3/4 hp 2-speed 115 V evaporative cooler motor, Electric Motor Warehouse
  11. Breezair EXT technical information (EXT 155, EXT 265), Seeley International
  12. Breezair Icon EXQ technical information (EXQ 170, EXQ 210), Seeley International
  13. Portacool Jetstream Series sell sheet, Portacool
  14. How To Convert A Swamp Cooler To Solar Powered, Hunker