What Size Generator Do You Need to Run a Swamp Cooler?
Running watts, starting watts and locked-rotor amps for 1/3 to 1 hp swamp coolers and Portacool portables, checked against a 2,200 W and a 3,000 W inverter generator.
Short answer
A 1/3 hp swamp cooler runs and starts on a 2,200 W inverter generator. A 1/2 hp cooler needs a 3,000 W class generator to cover its starting current, and a 3/4 hp cooler needs about 38 amps of surge at 120 V, roughly 4,600 W. A 240 V, 1 hp cooler needs a 120/240 V generator. The start, not the running load, sets the size.
Key takeaways
- Running load is small: about 740 W for a 1/3 hp cooler, 1,090 W for 1/2 hp and 1,310 W for 3/4 hp, counting nameplate amps at 120 V plus a 0.7 A pump.
- Generac's sizing rule puts starting load at 3 times horsepower in kW for motors under 7.5 hp: 1.0, 1.5 and 2.3 kW for 1/3, 1/2 and 3/4 hp.
- Generac also warns not to size on starting kW alone. Its table lists locked-rotor current of 25 A for a 1/2 hp motor and 38 A for 3/4 hp at 120 V, more than a Honda EU2200i's 18.3 A maximum.
- A 3/4 hp cooler passes the EU3000is watt test (2.3 kW start against 3,000 W max) but not the amp test (38 A against 25 A).
- Portable coolers are easier: most Portacool and Hessaire models draw 3.4 to 9.3 A, but the Jetstream 270 draws 15.2 A, needs a 20 amp outlet and outgrows a 2,200 W generator.
On this page
A 1/3 hp swamp cooler runs and starts on a 2,200 W inverter generator. A 1/2 hp cooler needs a 3,000 W class generator, and a 3/4 hp cooler needs one that can deliver about 38 amps at 120 V for the second it takes the motor to start, which works out to roughly 4,600 W of surge. A 1 hp cooler wired for 240 V needs a generator with 240 V output. In every case the start, not the running load, decides the size.
Below are the numbers for each motor size, checked against two common inverter generators. Wiring the permanent circuit is a separate question, covered in swamp cooler breaker and wire size.
Generator size by cooler motor
Running load comes from real motor nameplates, starting load and locked-rotor amps from Generac's sizing guide. The last column is the smallest generator that passes all three.
| Motor | Typical cooler | Running load | Starting load | Locked-rotor amps | Smallest generator that clears all three |
|---|---|---|---|---|---|
| 1/3 hp, 115 V | Champion 3000 | 740 W | 1,080 W | about 17 A at 120 V | 2,200 W inverter (EU2200i class) |
| 1/2 hp, 115 V | Champion 4001 | 1,090 W | 1,580 W | 25 A at 120 V | 3,000 W inverter (EU3000is class) |
| 3/4 hp, 115 V | Champion 5000 | 1,310 W | 2,330 W | 38 A at 120 V | About 4,600 W surge available at 120 V |
| 1 hp, 230 V | Large residential | 1,610 W | 3,000 W | 25 A at 240 V | 120/240 V generator, about 6,000 W surge |
The "typical cooler" pairings come from Champion's spec sheet for its 3000, 4001 and 5000 series, where the largest motor listed for each is 1/3, 1/2 and 3/4 hp respectively, all with the same 120 V, 0.7 A pump (part 110436). Your motor may differ; the swamp cooler motor guide explains how to read its nameplate.
How the running load is worked out
Running load is the blower's nameplate current on high speed plus the pump, times 120. Generac's sizing guide converts 120 V loads the same way, taking the worst-case power factor as 1.0. That matters on a small generator, whose rating is also a current: the Honda EU2200i is rated 1,800 W at 15 A.
| Motor | Nameplate (high / low) | Blower + pump | Running watts |
|---|---|---|---|
| Nidec 6767, 1/3 hp, 115 V | 5.5 / 3.9 A | 6.2 A | 740 W |
| Century SVB2054V1, 1/2 hp, 115 V | 8.4 A | 9.1 A | 1,090 W |
| Nidec 6770, 3/4 hp, 115 V | 10.2 / 4.7 A | 10.9 A | 1,310 W |
| Nidec 2423, 1 hp, 230 V | 7.0 / 3.7 A | 7.0 A (pump separate) | 1,610 W at 230 V |
These are lower than the 7.2, 9.8 and 13.8 A in Champion's spec tables, which are the National Electrical Code full-load figures used for sizing wire and breakers. For a generator, the nameplate is the better guide. If the motor pulley has been adjusted, check the draw with a clamp meter: a pulley opened past spec pushes current above nameplate, as belt and pulley adjustment explains.
Why the start sets the size
Two answers circulate. One says any small generator will do; the other says you need one as big as for an air conditioner. The first counts only running watts, which is right for a portable cooler and wrong for a belt-driven whole-house unit. The second overshoots: Champion Power Equipment's chart lists a window air conditioner at 1,200 running and 2,000 starting watts, more than a 1/3 or 1/2 hp cooler needs.
The deciding number is what the blower draws as it starts. Generac's rule for motors under 7.5 hp: starting kW equals horsepower times 3. Its method then adds the running load of everything else to the starting load of the largest motor.
Worked example: 1/2 hp cooler with nothing else running
Starting: 0.5 hp x 3 = 1.5 kW, plus 84 W for the pump, is about 1,580 W, inside a Honda EU2200i's 2,200 W maximum. Running: 1,090 W against its 1,800 W rating. It passes both.
That is where most generator advice stops, and where it goes wrong. Generac's guide warns: "DO NOT size the generator based on starting kW alone," and "YOU MUST compare LR Amps to generator surge capability." LR amps is locked-rotor current, drawn before the shaft turns.
The locked-rotor amp check
Generac's Table 1 lists locked-rotor current for single-phase motors at 120 V: 25 A for 1/2 hp, 38 A for 3/4 hp and 50 A for 1 hp. That is 50 A per horsepower, which puts a 1/3 hp motor near 17 A. At 240 V the figures halve. Compare those with the maximum current the generator can deliver:
| Check | Honda EU2200i | Honda EU3000is |
|---|---|---|
| Rated output | 1,800 W, 15 A | 2,800 W, 23.3 A |
| Maximum output | 2,200 W, 18.3 A | 3,000 W, 25 A |
| 1/3 hp: 740 W run, 1,080 W start, 17 A | Passes all three | Passes all three |
| 1/2 hp: 1,090 W run, 1,580 W start, 25 A | Passes watts, short on amps | Passes all three |
| 3/4 hp: 1,310 W run, 2,330 W start, 38 A | Short on starting watts and amps | Passes watts, short on amps |
| 1 hp, 230 V | No 240 V output | No 240 V output |
Note the 3/4 hp row. A 3,000 W inverter clears the starting-watts rule with 670 W to spare and still falls 13 A short. Clearing 38 A at 120 V takes about 4,600 W of surge on the 120 V output. On the EU3000is that also means using the 30 A locking receptacle rather than the 20 A duplex.
Falling short on amps does not prove a cooler will not start. Generac rates its own generators' surge capability at a voltage dip, limited to 30% for residential use, so some sag is expected. It means the start depends on how the generator handles a brief overload, which neither spec sheet states. The sizes in the first table do not leave it to chance.
Leave margin for everything else
Generac's worksheet adds 10 to 20% to the total for residential generators. During an outage the generator also carries a refrigerator, which Champion Power Equipment lists at 400 running and 2,200 starting watts: a bigger start than a 1/2 hp cooler blower.
Worked example: 1/2 hp cooler plus a refrigerator
Running load: 1,090 W + 400 W = 1,490 W. Starting load, by Champion Power Equipment's method of adding the highest single starting load to the total running watts: 2,200 + 1,490 = 3,690 W, plus 10 to 20% gives about 4,060 to 4,430 W. That is past an EU3000is. Starting the cooler first does not help, because the compressor cycles on by itself with the cooler already running.
Low speed helps: 3.9 A for the 1/3 hp Nidec and 4.7 A for the 3/4 hp Nidec, which frees capacity and stretches fuel. The EU2200i runs 3.2 hours on its 0.95 gallon tank at rated load and 8.1 hours at a quarter load. Two-speed wiring is covered in two-speed motor wiring.
Portable swamp coolers on a generator
Portable coolers list running current only. Champion Power Equipment's chart says starting watts "may be estimated at: 1-2x the running watts," so the table takes the high end.
| Model | CFM | Listed amps | Running watts | At 2x for starting | Generator |
|---|---|---|---|---|---|
| Portacool Jetstream 220 | 2,400 | 3.4 A | 410 W | 820 W | 2,200 W inverter |
| Hessaire MC61M | 5,300 | 4.3 A | 520 W | 1,030 W | 2,200 W inverter |
| Portacool Jetstream 250 | 8,500 | 6.6 A | 790 W | 1,580 W | 2,200 W inverter |
| Portacool Jetstream 230 | 3,600 | 8.3 A | 1,000 W | 1,990 W | 2,200 W inverter |
| Portacool Jetstream 260 | 12,500 | 9.3 A | 1,120 W | 2,230 W | 3,000 W inverter |
| Portacool Jetstream 270 | 22,500 | 15.2 A | 1,820 W | 3,650 W | Larger than 3,000 W |
The Jetstream 270 is the trap. Portacool notes it requires a 20 amp outlet, and at 15.2 A it exceeds the EU2200i's 15 A rating while running. The EU3000is runs it at 65% of its rating, but doubling for the start passes its 3,000 W maximum. For choosing a portable, see the portable evaporative cooler buying guide; for off-grid use without a generator, the 12 volt swamp cooler for an RV or van covers battery budgets.
Placing the generator and connecting the cooler
Ready.gov says generators should be used outdoors and "at least 20 feet away from windows, doors and attached garages." A swamp cooler adds a reason of its own: it pulls outdoor air through its pads and pushes it into the house, so a generator near the cooler's intake sends its exhaust indoors. Keep it well away from the cooler and from the open relief windows described in venting and relief air.
A portable cooler plugs in directly. A rooftop or wall cooler is hardwired, so generator power has to reach it through transfer equipment at the panel, which is electrician work.
Where these numbers stop applying
- Locked-rotor figures are general. Generac's table covers single-phase motors by horsepower, not cooler motors specifically, and none of the motor listings checked here publish locked-rotor amps. A nameplate figure, where present, overrides the table.
- A struggling motor is not a generator problem. A cooler that hums and will not start on utility power will not start on a generator either; see swamp cooler motor not running.
- Commercial and three-phase units are a different calculation.
For a cabin or workshop, running cost matters as much as size; swamp cooler operating cost has the energy math.
Frequently asked questions
Will a 2,000 watt generator run a swamp cooler?
It will run a 1/3 hp cooler and most portable coolers. A 1/2 hp whole-house cooler draws about 1,090 W running, within a 2,200 W inverter's 1,800 W rating, but Generac's table puts its locked-rotor current at 25 A, above the EU2200i's 18.3 A maximum. A 3/4 hp cooler needs more than a 2,000 W class generator.
How many watts does a swamp cooler use on a generator?
Multiply nameplate amps by 120 and add the pump. That gives about 740 W for a 1/3 hp cooler, 1,090 W for 1/2 hp and 1,310 W for 3/4 hp on high speed. Portable coolers range from about 410 W for a Portacool Jetstream 220 to about 1,820 W for a Jetstream 270.
Why does my swamp cooler stall or trip the generator on start-up?
A motor draws its locked-rotor current until it gets up to speed, several times its running current. Generac lists 25 A for a 1/2 hp motor and 38 A for a 3/4 hp motor at 120 V. If the generator cannot supply that, the voltage sags and the motor may not reach speed. Turn everything else off before starting the cooler, and check that the motor pulley is not opened past spec.
Can I run a 240 volt swamp cooler on an inverter generator?
Not on a 120 V only model such as the Honda EU2200i or EU3000is. A 240 V cooler needs a generator with 240 V output and transfer equipment to reach the hardwired circuit. A 1 hp, 240 V cooler needs about 3 kW of starting capacity by Generac's rule and 25 A of locked-rotor current at 240 V.
Where should the generator go when running a swamp cooler?
Outdoors and at least 20 feet from windows, doors and attached garages, as Ready.gov advises, and well away from the cooler itself. A swamp cooler pulls outdoor air through its pads and blows it into the house, so a generator near the cooler's intake feeds exhaust straight indoors.
Sources and further reading
- Generator Sizing Guide (Tables 1 and 3, sizing worksheet), Generac Power Systems, hosted by Home Power Systems
- Choosing a Generator: Wattage Chart, Champion Power Equipment
- Champion 3000, 4001 and 5000 DD/SD Specifications (motor and pump specifications), Champion Cooler (Essick Air), hosted by Appliance Factory Parts
- Nidec 6767, 1/3 hp 2-speed 115 V evaporative cooler motor, Electric Motor Warehouse
- Century SVB2054V1, 1/2 hp 2-speed 115 V evaporative cooler motor, Electric Motor Warehouse
- Nidec 6770, 3/4 hp 2-speed 115 V evaporative cooler motor, Electric Motor Warehouse
- Nidec 2423, 1 hp 2-speed 230 V evaporative cooler motor, Electric Motor Warehouse
- Honda EU2200i specifications, Sloan Implement (Honda dealer)
- Honda EU3000iS specifications, Sloan Implement (Honda dealer)
- Portacool Jetstream Series sell sheet (PARMKTLT305), Portacool
- Hessaire MC61M portable evaporative cooler, PartsSource
- Power Outages, Ready.gov (FEMA)