What Size Motor Does My Swamp Cooler Need?
Swamp cooler motor horsepower by model from Champion and MasterCool submittal sheets: 1/3 or 1/2 hp for a 4001, 1/2 or 3/4 hp for a 5000, with CFM at each duct static pressure.
Short answer
Use the horsepower printed on the cooler's serial plate. Champion lists 1/3 hp for a 3000, 1/3 or 1/2 hp for a 4001, and 1/2 or 3/4 hp for a 5000; MasterCool fits 3/4 hp to its 51 series and 1 hp to its 71 series. Where two sizes are listed and the cooler feeds ducts, take the larger: at 0.3 in of static pressure it moves 30 to 37 percent more air.
Key takeaways
- The cabinet, not the house, sets the motor size. Each Champion and MasterCool model accepts one or two horsepower ratings, printed on the serial plate and the submittal sheet.
- Where two sizes are allowed, the gap grows with duct resistance: 15 to 19 percent more air at zero static pressure, 30 to 37 percent at 0.3 in.
- Champion prints NR (no rating) for the 1/3 hp 4001 at 0.4 and 0.5 in of static pressure. On a long or undersized duct run, that motor is the wrong choice.
- The bigger motor only moves more air because it is set up to spin the blower faster. Swapping motors without opening up the pulley changes nothing but the amp draw.
- Champion's warranty excludes damage when a motor larger than the serial plate shows is used. Go to the top of the listed range, not past it.
On this page
Your swamp cooler needs the horsepower printed on its serial plate, and the cabinet decides it, not the size of the house. Champion's submittal sheets list 1/3 hp for a 3000, 1/3 or 1/2 hp for a 4001, and 1/2 or 3/4 hp for a 5000. MasterCool fits 3/4 hp to its 51 series and 1 hp to its 71 series. Where a model allows two sizes and the cooler feeds a duct system, buy the larger one. The tables below show why: the gap between the two is small with no ducts and large with them.
Motor size by model
These are the motor options each manufacturer lists for its own cabinets, with the National Electrical Code full-load amps the sheets print beside them. The Champion figures are for the blower motor alone; MasterCool's include the pumps.
| Cooler model | Listed motor | Amps at 115 V | Amps at 230 V |
|---|---|---|---|
| Champion 3000 DD/SD | 1/3 hp | 7.2 | Not listed |
| Champion 4001 DD/SD | 1/3 or 1/2 hp | 7.2 or 9.8 | Not listed |
| Champion 5000 DD/SD | 1/2 or 3/4 hp | 9.8 or 13.8 | Not listed |
| Champion 3000 RLD, 3001 RLD2 | 1/3 or 1/2 hp | 7.2 or 9.8 | 4.9 (1/2 hp) |
| Champion 4000 RLD, 4001 RLD2 | 1/3, 1/2 or 3/4 hp | 7.2, 9.8 or 13.8 | 4.9 or 6.9 |
| Champion 5000 RLD, 5001 RLD2 | 1/2, 3/4 or 1 hp | 9.8, 13.8 or 16 | 4.9, 6.9 or 8 |
| MasterCool C51, C5112 (AD/AS) | 3/4 hp, 2 speed | 14.9 with pumps | 7.5 with pumps |
| MasterCool C71, C7112 (AD/AS/AU) | 1 hp, 2 speed | 17.1 with pumps | 8.6 with pumps |
| Champion 75/85 SD | 3/4 or 1 hp | Varies by voltage and phase; see the commercial note below | |
| Champion 95 SD | 1-1/2 or 2 hp | Varies by voltage and phase; see the commercial note below | |
Two things in that table catch people out. First, a "4000" is not one cooler. The standard 4001 DD tops out at 1/2 hp, while the low-profile 4000 RLD and 4001 RLD2 accept up to 3/4 hp. Second, MasterCools ship with their motor fitted and only one size per model, so a replacement is a like-for-like swap. Read the full model on the data plate, including RLD, RLD2 or a 12 suffix, before you order anything; the same plate also picks the belt in the belt size chart.
Why the larger option wins on ducts
Champion's submittal sheet rates each motor option at six steps of external static pressure, from 0 to 0.5 in of water column. Static pressure is the resistance the ducts, registers and window openings put in the blower's way, and CFM explained covers how it is measured. Put the two motor options side by side and the pattern is plain.
| Static pressure (in) | 4001 DD, 1/3 hp | 4001 DD, 1/2 hp | 5000 DD, 1/2 hp | 5000 DD, 3/4 hp |
|---|---|---|---|---|
| 0 | 3,077 | 3,654 | 4,334 | 4,983 |
| 0.1 | 2,880 | 3,430 | 4,000 | 4,780 |
| 0.2 | 2,565 | 3,230 | 3,620 | 4,530 |
| 0.3 | 2,240 | 3,064 | 3,300 | 4,280 |
| 0.4 | NR | 2,498 | 2,610 | 4,020 |
| 0.5 | NR | 2,010 | 2,170 | 3,780 |
With no duct resistance, the bigger motor buys 19 percent more air on the 4001 and 15 percent more on the 5000. At 0.3 in, it buys 37 and 30 percent. At 0.4 in, the 5000's 3/4 hp moves 54 percent more than its 1/2 hp, and Champion prints NR instead of a figure for the 1/3 hp 4001. The side-discharge versions follow the same curve: the 4001 SD with 1/3 hp also shows NR from 0.4 in, and the 5000 SD with 1/2 hp shows NR at 0.5 in.
Which end of the table your house sits at depends on the ducts and the relief air. Essick's installation manual is blunt about both: extra long ducts cause static pressure and reduce airflow, and in most cases air conditioning duct work is too small for coolers. A downdraft cooler dropping straight into one ceiling diffuser, with windows open properly, sits near the left of the table. A cooler feeding branch ducts that were built for a furnace or refrigerated air sits toward the right, where the small motor runs out. The evaporative cooler ductwork guide covers duct sizing, and venting and relief air covers the window side. Champion's own rule for relief is at least 2 sq ft of opening per 1,000 CFM.
The box CFM is not the motor's CFM
This is the other reason owners pick the wrong motor. Retail listings for the Champion 4001 DD call it a 4,900 CFM cooler for 1,800 sq ft, motor not included, with 1/2 hp as the maximum. Champion's submittal sheet for the same cooler never gets near that: its best figure is 3,654 CFM, with the 1/2 hp motor and no duct at all, about 25 percent below the box. Champion's RLD manual uses 3,466 CFM for a 4001 RLD2 with 1/2 hp in its window-opening example.
So a rule of thumb that maps "4,900 CFM" to a motor size is starting from a number the cooler does not deliver on any motor its maker lists. The submittal figures are the ones measured against static pressure, and they are the ones to size from. The same goes for choosing the cooler in the first place; how to size a swamp cooler explains why delivered airflow is the figure that matters.
A bigger motor needs a faster blower to help
Look at the blower speeds on Champion's sheet and the extra airflow has a clear source. At 0.3 in, the 4001 DD's 1/3 hp row runs the blower at 440 rpm and the 1/2 hp row at 494 rpm. On the 5000 DD it is 363 against 411 rpm. The larger motor is rated with the blower turning about 12 to 13 percent faster, and fan power climbs steeply with speed, which is why that speed takes the extra horsepower.
The practical point: fitting a 1/2 hp motor in place of a 1/3 hp and leaving the adjustable pulley where it was gives you the same blower speed and the same air, with the new motor loafing. The airflow arrives when you close the pulley up to a larger working diameter. Champion's air balancing procedure, in its RLD manual, is the way to do that: start with the motor pulley at its smallest diameter, wet the pads, then step the pulley larger and re-measure until the motor draws its nameplate amps, never more. Essick gives the same instruction for its cabinets, in half-turn steps. The mechanics are in belt and pulley adjustment.
Worked example: a 4001 DD on a furnace duct
A 4001 DD feeds a duct system that once served a furnace, and an installer's manometer reads 0.3 in at the cooler outlet. With the 1/3 hp motor, Champion's sheet gives 2,240 CFM. With the 1/2 hp motor and the pulley set to nameplate amps, it gives 3,064 CFM: 824 CFM more, enough to matter in the back bedrooms. If the reading were 0.4 in, the choice would make itself: Champion does not rate the 1/3 hp there at all. The cost is current: 9.8 A against 7.2 A on a 115 V circuit, which the breaker and wire size guide shows still fits a 15 A circuit on 14 AWG.
Do not go past the serial plate
If the top listed motor still is not enough, the answer is not the next size up. Champion's RLD warranty excludes damage when a motor of a higher horsepower than the serial plate shows is used in the unit, and its 3000 to 6500 SM manual carries the same exclusion. Essick's warranty excludes a higher horsepower motor than it recommends. Beyond the warranty, the cabinet's blower, bearings, belt and wiring were rated for the listed range, and a 3/4 hp motor on a 4001 DD's drive has no row on Champion's sheet to tell you what it will do.
A cooler that cannot move enough air with its largest listed motor is usually fighting its ducts or its relief air, or it is simply too small for the house. Fix the restriction, or move up a cabinet size. The replacement motor guide covers the rest of the match once you know the horsepower: 1,725 rpm, frame, shaft diameter, speeds and rotation.
Pro tip: When you do step up within the listed range, check the circuit before the roof work. Going from 1/3 to 1/2 hp adds 2.6 A; going from 1/2 to 3/4 hp adds 4.0 A. A cooler sharing a circuit with anything else may need its own.
Where this chart stops applying
The tables cover Champion and MasterCool cabinets whose submittal sheets and manuals publish motor options. Phoenix Frigiking and Aerocool, Breezair and Bonaire units are not in them; use their own data plates. Direct-drive coolers, including many window units and portables, mount the blower wheel on the motor shaft, so the choice is the motor listed for that model rather than a horsepower step; see the swamp cooler motor guide for those.
Commercial cabinets are sized the same way but with heavier motors. Champion's sheet for the 75/85 SD lists 3/4 or 1 hp: 5,905 against 6,498 CFM with no duct, and 4,456 against 5,233 CFM at 0.5 in, so the larger motor again pulls further ahead as resistance rises. The 95 SD takes 1-1/2 or 2 hp, at 6,868 and 7,558 CFM with no duct. Larger cabinets run on 230 V or three-phase motors whose amps vary by voltage; quote the motor part number from the sheet, and see the commercial cooling guide for how those systems are specified.
Finally, the amps in the first table are National Electrical Code values, which is what the sheets print and what circuits are sized from. The actual motor you buy has its own nameplate figure, and that is the number to set the pulley against. If you are planning for outages, the generator sizing guide works from the same horsepower ratings.
Frequently asked questions
What size motor does a Champion 4001 swamp cooler take?
Champion's submittal sheet lists 1/3 hp (7.2 A at 115 V) or 1/2 hp (9.8 A) for the 4001 DD and SD. The 1/2 hp delivers 3,064 CFM at 0.3 in of static pressure on the downdraft, against 2,240 CFM for the 1/3 hp.
Can I put a 3/4 hp motor on a 4000 or 4001 cooler?
Not on the standard 4001 DD or SD: Champion's sheet lists only 1/3 and 1/2 hp for it. The low-profile 4000 RLD and 4001 RLD2 are a different cabinet, and Champion's manual for those lists 1/3, 1/2 and 3/4 hp. Read the model on the serial plate before buying.
Is a 1/3 hp motor enough for a swamp cooler?
On a 3000 series it is the only size Champion lists. On a 4001 it works for a short duct with plenty of window opening, but it loses more air than the 1/2 hp as duct resistance rises, and Champion gives it no rating at all at 0.4 in or more.
Will a bigger motor make my swamp cooler blow colder air?
No. A cooler's outlet temperature is set by the pads and the outdoor wet bulb. A larger listed motor moves more air, which cools more of the house, but only when the pulley is set to spin the blower faster.
Does the CFM on the box tell me which motor to buy?
No. The box rating for a Champion 4001 DD is 4,900 CFM, but Champion's own submittal sheet shows that cooler delivering at most 3,654 CFM, with the 1/2 hp motor at zero static pressure. Size the motor from the model, not the box figure.
Sources and further reading
- Champion 3000, 4001 and 5000 DD/SD Specifications and Submittal Data (motor specifications and CFM at static pressure), Champion Cooler
- Champion 3000/4000/5000 RLD and RLD2 Owner's Manual (motor specifications, air balancing, warranty), Champion Cooler
- MasterCool AD/AS C51, C5112, C71 and C7112 Specifications and Submittal Data (electrical specifications and CFM), Champion Cooler
- Champion 75/85 SD, 95 SD, 10/12 SD and 14/21 SD Specifications and Submittal Data (side discharge performance), Champion Cooler
- Essick 15000 Owner's Manual (duct work, start up, warranty), Essick Air Products
- Champion 3000, 4000, 4500, 5500 and 6500 SM Owner's Manual (warranty), Champion Cooler
- Champion Cooler 4001 DD: 4900 CFM Down Draft Roof Evaporative Cooler for 1800 sq ft, Motor Not Included (retail listing specs), mans.io