How Many Tons Is a Swamp Cooler?
A swamp cooler is about 3 to 4 tons of AC-equivalent cooling on a dry day, per Breezair's test. Why pad-drop math says 10, plus a CFM to tons chart.
Short answer
On a hot, dry day a typical whole-house swamp cooler delivers about 3 to 4 tons of room cooling. Breezair rates its EXQ170 at 37,580 BTU/h (3.1 tons) and its EXQ210 at 46,070 BTU/h (3.8 tons), measured to the room exit air. Math that counts the full drop across the pads gives about 10 tons for the same cooler, but most of that only cancels the heat of the outdoor air it pulls in.
Key takeaways
- One ton of cooling is 12,000 BTU/h. Breezair's US sheet rates the EXQ170 at 37,580 BTU/h (3.1 tons) and the EXQ210 at 46,070 BTU/h (3.8 tons), at 0.3 in static, 100.4 F dry bulb and 69.8 F wet bulb.
- Those ratings come from 4,430 and 5,400 CFM, the fan table's airflow at 0.3 in, not the 7,500 and 9,500 CFM printed as the 'industry standard' figure.
- For AC-equivalent tons, use room cooling: about 8.5 BTU/h per delivered CFM on a hot, dry day, or tons = CFM x 8.5 / 12,000. A cooler delivering 4,500 CFM is about 3.2 tons.
- The pad drop (outdoor minus supply) gives about 3.4 times as much, because most of it only cools outdoor air down to the supply temperature. It sets water use, not the tons the house gets.
- Cooler tons are all sensible. An AC's nominal tons include latent (moisture) removal: Goodman's 3-ton GPC1436 is rated 35,000 BTU/h total but 27,000 BTU/h sensible. Champion and MasterCool publish no BTU rating at all.
On this page
A whole-house swamp cooler is about 3 to 4 tons of air conditioning on a hot, dry day. That is the figure the one maker who publishes a rating gets. Breezair rates its Icon EXQ170 at 37,580 BTU/h, or 3.1 tons, and its EXQ210 at 46,070 BTU/h, or 3.8 tons. The other answer you will find is much bigger. Run the same cooler through the drop across its pads and you get about 10 tons. The small number is the one to compare with an AC. This page shows why, and gives a CFM to tons chart for both methods.
What a "ton" of cooling means
A ton is a rate of cooling, not a weight. ACHR News defines it as the heat absorbed in melting one ton of ice in 24 hours. That works out to 12,000 BTU per hour. So:
Air conditioners are sold by the ton. A "3-ton" unit is built to remove about 36,000 BTU/h. Swamp coolers are sold by airflow in CFM (cubic feet per minute) instead, because their cooling changes with the weather. That is why how to size a swamp cooler works in air changes, not tons. But people shopping between the two want one number to compare. Getting it takes two more terms.
Sensible cooling lowers the air temperature. You feel it on a thermometer. Latent cooling removes moisture from the air. An AC does both: its cold coil chills the air and also wrings water out of it. A swamp cooler does only the first. It adds moisture rather than removing it. So a cooler's tons are always sensible tons.
The figure Breezair publishes
Seeley International's US sheet for the Breezair Icon EXQ lists a cooling capacity at 0.3 in of static pressure (IWG, inches of water gauge). It says the capacity was "measured to Australian Standard AS2913-2000" on a 100.4 F dry bulb, 69.8 F wet bulb day, with a room exit temperature of 81.3 F. The room exit temperature is the temperature of the air as it leaves the house through the windows or relief vents.
| Model | "Industry standard" CFM | Fan table CFM at 0.3 in | Cooling capacity at 0.3 in | Tons (BTU/h / 12,000) |
|---|---|---|---|---|
| EXQ170 | 7,500 | 4,430 | 37,580 BTU/h | 3.1 |
| EXQ210 | 9,500 | 5,400 | 46,070 BTU/h | 3.8 |
Read the two CFM columns carefully. The sheet prints 7,500 and 9,500 CFM on the same page as the capacity. But its own fan table gives 4,430 and 5,400 CFM at 0.3 in. Even at zero static it gives only 5,000 and 5,830. The capacity matches the fan table, not the bigger label. Divide 37,580 by 4,430 and you get 8.5 BTU/h per CFM. Divide it by 7,500 and you get 5.0, which would make every cooler look weaker than it is. CFM explained covers why delivered airflow falls as static pressure rises.
Seeley does not print the formula behind the rating, but the numbers fit the site's room cooling equation. The sheet's discharge chart uses an 87% saturation efficiency. On the test day that gives supply air of about 73.8 F, and the room exit is 81.3 F. That is a gap of about 7.5 F. The rating implies a gap of 7.9 F (37,580 / (1.08 x 4,430)). The two agree within half a degree.
Why pad-drop math gives three times as much
The site uses one equation for both cooling and water use:
The answer depends on which temperature difference you feed it.
- Across the pads (outdoor minus supply). On Seeley's test day this is 100.4 - 73.8 = 26.6 F. This is the heat the water absorbs as it evaporates. It is the right figure for water usage.
- Across the house (room exit minus supply). This is about 7.5 to 7.9 F on the same day. It is the heat the air picks up inside the house before it leaves. This is what Breezair rates.
The first number is real, but most of it never reaches the house. A cooler pulls in 100 F outdoor air. The pads spend most of their work bringing that air down to 74 F. Only then does the air start to absorb heat from the rooms. An air conditioner does not have this problem. It recirculates indoor air at about 80 F, so its whole rating goes to the house. To compare a cooler with an AC, count only the part that cools the house: the room exit method.
The ratio between the two methods is about 3.4 on Seeley's test day (26.6 / 7.9). It is not fixed. It changes with the weather and with how warm you let the house get.
CFM to tons chart: both methods
CFM here means delivered airflow, the figure from a fan table at your static pressure, not the label on the box. The desert day is Seeley's test day: 100.4 F dry bulb and 69.8 F wet bulb, with 87% media and sea-level air. The room exit column uses the 8.5 BTU/h per CFM that Breezair's ratings work out to.
| Delivered CFM | Room exit method (AC-equivalent) | Tons | Pad drop method (26.6 F) | Tons |
|---|---|---|---|---|
| 3,000 | 25,500 BTU/h | 2.1 | 86,200 BTU/h | 7.2 |
| 4,000 | 34,000 BTU/h | 2.8 | 114,900 BTU/h | 9.6 |
| 5,000 | 42,500 BTU/h | 3.5 | 143,600 BTU/h | 12.0 |
| 6,000 | 51,000 BTU/h | 4.2 | 172,400 BTU/h | 14.4 |
| 7,000 | 59,500 BTU/h | 5.0 | 201,100 BTU/h | 16.8 |
A humid day shrinks both numbers. Seeley's discharge chart gives 77 F supply air on a 90 F day at 50% relative humidity. The pad drop falls to 13 F. If you want to hold the house at the same 81.3 F, the room gap falls to 4.3 F.
| Day | Supply air | Room exit method (house at 81.3 F) | Pad drop method |
|---|---|---|---|
| Desert: 100.4 F, 69.8 F wet bulb | 73.8 F | 42,500 BTU/h (3.5 tons) | 143,600 BTU/h (12.0 tons) |
| Humid: 90 F, 50% RH | 77 F | 23,200 BTU/h (1.9 tons) | 70,200 BTU/h (5.8 tons) |
On the humid day the same cooler is worth about half as many tons. That is the whole reason makers sell coolers by CFM. For how the supply temperature follows the weather, see wet bulb temperature explained.
Worked example: a MasterCool ADA7112 labeled 7,000
Take a MasterCool ADA7112 with a 1 hp motor. Its spec sheet gives an "industry standard rating" of 7,000. Its CFM table gives 4,394 CFM at 0.3 in of static pressure. MasterCool publishes no efficiency or BTU figure, so suppose its 12 in media matches the 87% Seeley uses.
Using the label: 7,000 x 8.5 = 59,500 BTU/h, or 5.0 tons. That overstates it.
Using delivered airflow on the desert day: 4,394 x 8.5 = 37,300 BTU/h, or 3.1 tons.
The pad drop on the same day: 1.08 x 4,394 x 26.6 = 126,200 BTU/h, or 10.5 tons. That much heat goes into evaporating about 14 gallons of water an hour (4,394 x 26.6 / 8,186).
On the humid day, holding the house at 81.3 F: 1.08 x 4,394 x 4.3 = 20,400 BTU/h, or 1.7 tons.
So the honest answer for this cooler is about 3 tons on a dry afternoon and under 2 tons on a sticky one.
Comparing cooler tons with AC tons
An air conditioner's nominal tons include latent cooling. Goodman's GPC1436, a 3-ton packaged unit, is rated at 35,000 BTU/h total but 27,000 BTU/h sensible. The 8,000 BTU/h between them is spent pulling water out of the air. So the part of that "3-ton" unit you feel on a thermometer is about 2.25 tons.
Goodman's expanded cooling table shows the split moving with indoor humidity. With an 80 F house and a 95 F day, the sensible share is 1.00, or close to it, when the indoor wet bulb is 59 F (dry air). It falls to about 0.6 when the indoor wet bulb is 71 F (humid air). In a dry Western house, more of an AC's capacity goes to temperature.
Put the two sheets side by side and the Breezair EXQ170's 37,580 BTU/h is more sensible cooling than the 3-ton Goodman's 27,000. But they were not tested the same way. The Goodman is AHRI certified, and AHRI's test day is not AS2913's. Treat the match as rough. Roughly, on a dry day:
- About 3,200 delivered CFM matches the 27,000 BTU/h sensible rating of a 3-ton AC (27,000 / 8.5).
- About 4,100 delivered CFM matches its 35,000 BTU/h total rating (35,000 / 8.5).
One more shortcut is worth naming, because it inflates the answer. Goodman's 3-ton unit moves a nominal 1,200 CFM, or 400 CFM per ton. Divide a cooler's 4,500 CFM by 400 and you get 11 tons. That rule is for AC air, which leaves the coil far colder than cooler air. It does not apply to a swamp cooler. The full trade-off between the two systems is in swamp cooler vs air conditioner.
Champion and MasterCool publish no BTU rating
Most coolers sold in the US have no ton or BTU figure at all. Champion's submittal sheet for the 3000, 4001 and 5000 DD and SD lists CFM and blower rpm at 0 to 0.5 in of static pressure, with motor amps and dimensions. It prints no BTU/h. MasterCool's ADA51, ADA5112, ADA71 and ADA7112 sheet lists an "industry standard rating" of 4,000 to 7,000, a coverage area of 1,100 to 2,300 sq ft, and CFM at 0 to 0.6 in. It prints no BTU/h either. Its coverage line carries the footnote "Coverage area depends on outdoor conditions."
For these coolers, take the CFM at your static pressure from the fan table and use the chart above. A 0.3 in figure is a fair start for a short duct. The Champion vs MasterCool page lists each model's 0.3 in airflow. The Breezair guide covers the brand that does print a rating.
Where these numbers stop applying
The 8.5 BTU/h per CFM figure belongs to one test day: 100.4 F outside, a 69.8 F wet bulb, 87% media and a house that lets the air leave at 81.3 F. Change any of those and the tons change. A wetter day, older aspen pads or a cooler house all lower it. The 1.08 constant also assumes sea-level air. At Denver's 5,400 ft it is about 18% lower, though the colder wet bulb wins back most of that, as swamp coolers at high altitude shows. The chart is for comparing a cooler with an AC. It is not a load calculation and does not tell you whether one cooler can hold your house. For that, size by air changes. Last, a cooler only delivers its CFM if the house lets the same air out. With too little open window, delivered airflow and tons both fall (see venting and relief air).
Frequently asked questions
How many tons is a 4,500 CFM swamp cooler?
If 4,500 CFM is the air it actually delivers, about 3.2 tons of room cooling on a 100 F day with a 70 F wet bulb, and about 1.7 tons on a 90 F day at 50% humidity with the house held near 81 F. If 4,500 is only the number on the box, it delivers less. Most box ratings are well above the airflow at 0.3 in of static pressure.
How many BTU is a swamp cooler?
Breezair is the only maker in this comparison that publishes one: 37,580 BTU/h for the EXQ170 and 46,070 BTU/h for the EXQ210 on a 100.4 F, 69.8 F wet bulb test day. For other coolers, multiply delivered CFM by about 8.5 for a hot, dry day.
Can a swamp cooler replace a 3 ton air conditioner?
In dry weather, a whole-house cooler delivering about 3,200 CFM matches the 27,000 BTU/h of sensible cooling Goodman rates its 3-ton packaged unit for, and about 4,100 CFM matches its 35,000 BTU/h total. The two are rated under different test conditions, and on humid days the cooler's figure about halves.
Why do CFM to tons calculators give such big numbers for swamp coolers?
Two common shortcuts inflate the answer. One counts the whole temperature drop across the pads, which is about 3.4 times the room cooling on a dry day. The other divides by 400 CFM per ton, an air conditioner airflow rule, which turns 4,500 CFM into about 11 tons.
Do Champion or MasterCool coolers have a BTU rating?
No. Champion's 3000, 4001 and 5000 submittal sheet lists CFM at 0 to 0.5 in of static pressure. MasterCool's ADA spec sheet lists an industry standard rating, coverage in square feet and CFM at 0 to 0.6 in. Neither prints BTU/h or tons.
Sources and further reading
- Breezair Icon EXQ technical information, US brochure (cat. no. B0808 rev B), Seeley International
- Specifications and Submittal Data: 3000, 4001, 5000 DD and SD (8-08), Champion Cooler
- ADA51, ADA5112, ADA71, ADA7112 specifications, MasterCool
- GPC14M Packaged Air Conditioner specifications (SS-GPC14M), Goodman Manufacturing
- Understanding What a Cooling Ton Means (John Tomczyk, March 4, 2021), ACHR News