Do Swamp Coolers Work at High Altitude?
Swamp coolers at altitude: density factors and BTU/h per 1,000 CFM for six Mountain West cities, the 2 F lower wet bulb, and why to add 4 to 11% CFM, not 22%.
Short answer
Yes. A cooler moves the same CFM at 5,400 ft as at sea level, but each CFM carries about 18% less heat, so the 1.08 constant becomes 0.885 in Denver. Lower pressure also drops the wet bulb about 2 F, making the supply air colder. Net, a Denver cooler delivers 5 to 8% less cooling than sea-level math predicts, not 18%.
Key takeaways
- The 1.08 in BTU/h = 1.08 x CFM x drop assumes sea-level air. Multiply it by the density factor (1 - 0.00000687 x ft)^5.256: 0.86 in Salt Lake City, 0.82 in Albuquerque and Denver, 0.80 in Colorado Springs and Santa Fe, 0.77 in Flagstaff.
- At a fixed 20 F drop, 1,000 CFM carries 21,600 BTU/h at sea level and about 17,700 BTU/h in Denver, so holding the same drop takes 22% more air.
- At the same dry bulb and dew point, the wet bulb is 1.7 to 2.8 F lower in these six cities than a sea-level chart says (95 F, 40 F dew point), so an 85% pad makes air 1.4 to 2.4 F colder.
- Net of both effects, a cooler in these cities needs about 4 to 8% more airflow than sea-level math on a dry afternoon and 6 to 11% more on a humid one, not the 17 to 30% the density factor alone suggests.
- Water use falls with the air density: about 12% less per CFM in Denver than the sea-level formula predicts.
On this page
- What thin air changes, and what it does not
- Density factor and heat per 1,000 CFM by city
- The lower wet bulb: the half most sizing pages leave out
- Net effect: how much more airflow to buy
- Where the 20% figure comes from, and why it is the wrong one for coolers
- Water use at altitude
- Why mountain cities still suit coolers so well
- Where these numbers stop applying
- Frequently asked questions
Yes, swamp coolers work at high altitude. Thin air does cost something: each cubic foot carries less heat, about 18% less at Denver's 5,400 ft. But the same low pressure drops the wet bulb about 2 F, so the pad makes colder air. Put the two together and a cooler in Denver delivers about 5 to 8% less cooling than sea-level math predicts, not 18%. This page gives both numbers for six Mountain West cities and shows how much airflow to add.
What thin air changes, and what it does not
A blower is a volume machine. Spinning at the same speed, it moves the same cubic feet per minute in Flagstaff as in Yuma, so the maker's rated CFM and the air change math in how to size a swamp cooler still describe the air you get. ACHR News, in an ACCA article on high-altitude equipment, says it plainly: "One cfm of air is always 1 cfm, no matter what the elevation. Air at high elevations is less dense and carries less heat."
The second sentence is what changes the cooling formula the site's sizing pages use:
The 1.08 is built on the weight of a cubic foot of sea-level air, as CFM explained notes. At altitude the cubic foot weighs less, so the constant shrinks in proportion. CaptiveAire gives the standard correction as a density factor:
CaptiveAire puts it at "approximately 0.83" at 5,000 ft. ACHR News arrives at the same place from the other end: 1,200 CFM carries 36,000 BTU/h at sea level, and about 1,430 CFM is needed at 5,000 ft to carry the same heat, a ratio of 0.84.
Density factor and heat per 1,000 CFM by city
Elevations are the National Weather Service station heights at each city's main airport, converted from meters. The last column is how much more air it takes to carry the same heat at the same temperature drop.
| City (NWS station) | Elevation | Density factor | Constant (1.08 x factor) | BTU/h per 1,000 CFM | More CFM for the same heat |
|---|---|---|---|---|---|
| Sea level | 0 ft | 1.000 | 1.080 | 21,600 | 0% |
| Salt Lake City (KSLC) | 4,226 ft | 0.857 | 0.925 | 18,500 | 17% |
| Albuquerque (KABQ) | 5,351 ft | 0.821 | 0.887 | 17,700 | 22% |
| Denver (KDEN) | 5,404 ft | 0.820 | 0.885 | 17,700 | 22% |
| Colorado Springs (KCOS) | 6,186 ft | 0.796 | 0.860 | 17,200 | 26% |
| Santa Fe (KSAF) | 6,260 ft | 0.794 | 0.857 | 17,100 | 26% |
| Flagstaff (KFLG) | 6,994 ft | 0.772 | 0.834 | 16,700 | 30% |
That table holds the temperature drop fixed at 20 F. At altitude the drop is not fixed.
The lower wet bulb: the half most sizing pages leave out
A cooler's supply air approaches the wet bulb temperature. The wet bulb depends on pressure as well as on temperature and moisture: at lower pressure, water evaporates into the air more readily, so the same dry bulb and the same dew point give a lower wet bulb. A calculator that takes no pressure input gives the sea-level wet bulb, which overstates it at altitude.
The figures below were computed with PsychroLib, an open source library that implements the psychrometric equations of the ASHRAE Handbook Fundamentals (2017) and takes the station pressure as an input. The pressure at each elevation is the ASHRAE standard atmosphere, the same curve the density factor above comes from. The test afternoon is 95 F with a 40 F dew point (15% RH), and the pad is rigid media at 85% efficiency.
| Location | Wet bulb | Lower than sea-level chart by | Supply air | Drop across the pad |
|---|---|---|---|---|
| Sea-level chart | 63.3 F | 0 | 68.1 F | 26.9 F |
| Salt Lake City | 61.6 F | 1.7 F | 66.6 F | 28.4 F |
| Albuquerque | 61.2 F | 2.2 F | 66.3 F | 28.7 F |
| Denver | 61.2 F | 2.2 F | 66.2 F | 28.8 F |
| Colorado Springs | 60.9 F | 2.5 F | 66.0 F | 29.0 F |
| Santa Fe | 60.8 F | 2.5 F | 65.9 F | 29.1 F |
| Flagstaff | 60.5 F | 2.8 F | 65.7 F | 29.3 F |
On a muggier 90 F afternoon with a 55 F dew point (31% RH), the gap is smaller: 1.1 F in Salt Lake City, 1.4 F in Denver and 1.8 F in Flagstaff. The site's older rule of thumb, wet bulbs "roughly 1 to 2 F lower" at 5,000 ft, holds; at 6,000 to 7,000 ft the dry-day figure runs to 2.5 to 2.8 F.
A couple of degrees matters because the cooling a house gets depends on the gap between room and supply air. If you hold the house at 80 F, sea-level math says Denver's supply air at 68.1 F leaves 11.9 F of headroom. The real 66.2 F leaves 13.8 F, 16% more. That is most of the 18% the density factor took away. The site's cooling temperature calculator uses a sea-level wet bulb formula with no pressure input, so at altitude subtract the gap in this table from its wet bulb.
Net effect: how much more airflow to buy
Worked example: the Denver house from the sizing guide
The sizing guide's Denver example needs 6,050 CFM delivered. On the 95 F, 40 F dew point day with the house at 80 F:
Sea-level math: 1.08 x 6,050 x (80 - 68.1) = about 77,750 BTU/h.
At Denver's pressure: 0.885 x 6,050 x (80 - 66.2) = about 73,900 BTU/h, 5% less.
To carry the full 77,750 BTU/h at Denver's pressure takes 77,750 / (0.885 x 13.8) = about 6,370 CFM, 320 more. Not the 1,330 more that the density factor alone (6,050 / 0.820) would ask for.
The same calculation for each city, at two kinds of afternoon:
| City | Same drop (density factor only) | Dry day: 95 F, 40 F dew point | Humid day: 90 F, 55 F dew point |
|---|---|---|---|
| Salt Lake City | 17% | 4% | 6% |
| Albuquerque | 22% | 6% | 8% |
| Denver | 22% | 6% | 8% |
| Colorado Springs | 26% | 7% | 9% |
| Santa Fe | 26% | 7% | 10% |
| Flagstaff | 30% | 8% | 11% |
So the answer to "how much bigger" is about 4 to 11%, rising with elevation and humidity. If you sized with the site's air change rates, that margin already fits inside the 20 to 25% of moderate oversizing the sizing guide calls fine: pick the model at or just above your calculated CFM rather than one just under it. The cooler size calculator gives the starting figure; it does not apply an altitude correction.
Where the 20% figure comes from, and why it is the wrong one for coolers
The density factor is correct, and the ACHR News article applies it directly, because furnaces and air conditioners are judged on the temperature change across a coil or heat exchanger, which altitude does not enlarge. An evaporative cooler's supply temperature is set by the wet bulb, and the wet bulb moves the cooler's way as pressure falls. Correcting the 1.08 without also using a wet bulb at your own pressure applies half the physics and overstates the penalty roughly threefold.
A second figure circulates too. The Bonneville Power Administration's airflow test instructions say that at 5,000 ft "approximately a 10% bump in volumetric flow is needed to provide the same mass flow as at sea level." For the same mass of air the density factor gives about 20% (1 / 0.83), and ACHR's 1,200 to 1,430 CFM is 19%, so the 10% figure understates that particular correction.
Water use at altitude
Water evaporated tracks the heat the air gives up, which is mass of air times drop. In Denver on the dry test day, sea-level math puts the 6,050 CFM cooler at about 19.9 gal/h of evaporation; at Denver's pressure it is about 17.4 gal/h, 12% less, before bleed-off. The water usage calculator and the figures in swamp cooler water usage use the sea-level 1.08, so at 5,000 to 7,000 ft read them as an upper bound: the real figure is about 12 to 16% lower.
Why mountain cities still suit coolers so well
In practice altitude is no handicap, because the weather up there is milder. The site's climate index lists a design dry bulb of 91 F for Denver and 85 F for Flagstaff against 110 F for Phoenix, and design wet bulbs of 59 and 56 F against 70 F. A cooler facing a 5% heat-carrying shortfall on a 91 F day is far better off than a Phoenix cooler facing 110 F. That is why best climates for swamp coolers rates the Front Range, the Wasatch Front and high-desert New Mexico among the best places to own one, and why the main exception is the monsoon, covered in swamp coolers during monsoon season.
Where these numbers stop applying
- Your elevation is not the airport's. The table uses NWS airport stations. Plug your own elevation into the density factor; each 1,000 ft changes it by roughly 0.03 in this range.
- The net figures depend on the room temperature. They assume the house is held at 80 F. Aim for a cooler house and the 2 F wet bulb gain is a bigger share of a smaller headroom, so the penalty shrinks; tolerate a warmer house and it grows toward the density-factor figure. The pressure at each elevation is the standard atmosphere, not the day's barometer reading.
- Use dew point, not RH, when comparing places. The wet bulb gain is computed at the same dew point. A weather report already measured at your elevation needs no correction; only a calculator or chart that assumes sea-level pressure does.
Frequently asked questions
Does a swamp cooler blow less air at high altitude?
No. A blower moves the same volume of air at any elevation, so the cooler's rated CFM still applies. As ACHR News puts it, one cfm of air is always 1 cfm. What changes is how much heat each cubic foot carries.
Do swamp coolers work better at high altitude?
The supply air is colder: at the same temperature and dew point, the wet bulb in Denver is about 2 F lower than at sea level. But each CFM carries about 18% less heat, so per CFM a high-altitude cooler removes slightly less heat than the same weather would allow at sea level. The bigger advantage of mountain cities is their weather: dry air and cool nights.
How much bigger a swamp cooler do I need in Denver?
About 6 to 8% more delivered CFM than a sea-level calculation gives, if you enter your weather at Denver's pressure. If you hold the temperature drop fixed and only correct the 1.08 constant, the figure is 22%, but that ignores the colder supply air the lower pressure gives you.
Does altitude affect the wet bulb temperature?
Yes. At lower pressure the same dew point gives a lower wet bulb. At 95 F with a 40 F dew point the wet bulb is 63.3 F at sea level, 61.2 F at Denver's airport (5,404 ft) and 60.5 F at Flagstaff's (6,994 ft).
Do swamp coolers work at 7,000 feet?
Yes. Flagstaff, at 6,994 ft, has a design dry bulb of 85 F, so a cooler there seldom runs short. At 7,000 ft the density factor is about 0.77, so 1,000 CFM at a 20 F drop carries about 16,700 BTU/h instead of 21,600, but the lower wet bulb wins back most of that.
Sources and further reading
- Cooling Density Factor (formula and 5,000 ft value), CaptiveAire Systems
- Selecting Heating, Cooling Units for High-Altitude Homes (ACCA, March 30, 2009), ACHR News
- PsychroLib 2.5.0: psychrometric functions from ASHRAE Handbook Fundamentals (2017), chapter 1, PsychroLib contributors (Journal of Open Source Software, doi 10.21105/joss.01137)
- Station metadata and elevation for KSLC, KABQ, KDEN, KCOS, KSAF and KFLG, NOAA National Weather Service API
- Airflow Test (Detailed Instructions), PTCS, Bonneville Power Administration