Pumps and Water

What Size Pump Does a Swamp Cooler Need?

Swamp cooler pump size by CFM, with GPH at 1, 3 and 6 ft of lift from Dial and Little Giant data, and the pad wetting flow each Champion cooler needs.

Short answer

Buy a pump rated for at least your cooler's CFM, in the same voltage. A 4,000 to 5,000 CFM home cooler takes a 5,500 to 7,500 CFM class pump: 240 to 360 GPH on the box, about 205 to 315 GPH at the 3 ft lift inside the cabinet. Above 12,000 CFM, use a 505 to 580 GPH industrial pump.

Key takeaways

  • Pump makers size pumps by cooler CFM, not by GPH. Match the CFM label to the cooler's rated CFM and the voltage to the old pump.
  • The GPH on Dial and Little Giant boxes is flow at 1 ft of lift, not zero. At a 3 ft lift concentric pumps lose 9 to 15 percent and offset pumps up to 27 percent.
  • Dial's offset UL10000 is labeled for a bigger cooler than its concentric UL7500 but moves less water at every height: 290 against 360 GPH at 1 ft, 130 against 205 at 6 ft.
  • Champion fits one pump, part 110436 at 120 V and 0.7 A, to every 3000, 4001 and 5000 cooler. Residential pumps are not finely graded by cooler size.
  • Pad wetting rates from university extension guides put a Champion 4001 downdraft at roughly 165 to 185 GPH, so a 7,500 class pump has at least 70 percent margin and a 5,500 class pump is close to the line on a 5000.
On this page
  1. Pump size by cooler CFM
  2. The GPH on the box is flow at 1 ft
  3. Offset and concentric labels are not comparable
  4. How much water the pads actually need
  5. Rigid media, window and commercial coolers
  6. Voltage and current
  7. Too big, too small, and the purge pump
  8. Where these numbers stop applying
  9. Frequently asked questions

A swamp cooler needs a pump rated for at least its own CFM, in the same voltage as the old one. Pump makers do not ask you to work out gallons per hour: Dial and Little Giant both label their pumps by the cooler size they serve. For the common 4,000 to 5,000 CFM home cooler, that is a 5,500 to 7,500 CFM class pump. What the label does not tell you is how much water reaches the pads once it has climbed the cabinet, and that is where most of the bad advice about pump size comes from.

For the cord, bracket and fittings, see choosing a replacement pump; if the old pump may not be dead, start with swamp cooler pump not working.

Pump size by cooler CFM

The table puts Dial's current pump line and Little Giant's CP series side by side, with flow at three lift heights. Dial's 1 ft figures are its catalog ratings; the 3 ft and 6 ft figures are read from Dial's published flow chart, to the nearest 5 GPH. Little Giant prints its figures at 1, 3 and 5 ft.

Cooler pump flow by rated cooler size and lift height
Pump (design)Rated cooler sizeGPH at 1 ftGPH at 3 ftGPH at 5 or 6 ft
Dial UL5000 (offset)5,000 CFM22516565 at 5 ft (top of curve)
Dial UL5500 (concentric)5,500 CFM24020590 at 6 ft
Dial UL7000 (offset)7,000 CFM25020580 at 6 ft
Dial UL10000 (offset)10,000 CFM290245130 at 6 ft
Dial UL7500 (concentric)7,500 CFM360315205 at 6 ft
Dial UL11000 (concentric)11,000 CFM420380280 at 6 ft
Dial UL15000LA (concentric)12,000 to 21,000 CFM505450340 at 6 ft
Dial UL25000LA (concentric)15,000 to 25,000 CFM580525410 at 6 ft
Little Giant CP17,000 CFM307265213 at 5 ft
Little Giant CP2Not stated per model502440371 at 5 ft
Little Giant CP3Series rated up to 21,000 CFM563512460 at 5 ft

Read the rated size against your cooler's box or data plate rating, not its delivered airflow. The two differ a lot: a Champion 4001 DD is sold as a 4,900 CFM cooler but Champion's own sheet shows at most 3,654 CFM, as the motor size chart explains. A pump rated 5,500 CFM or more covers it either way. CFM explained covers the difference.

The GPH on the box is flow at 1 ft

Two claims circulate: that the GPH rating is measured with no lift at all, and that it is the real flow you will get. Neither fits the published data. Dial's catalog figures match the 1 ft point on its own flow chart for every pump (the UL7500's 360 GPH, the UL11000's 420, the UL15000LA's 505), and Little Giant states its ratings "@ 1 ft". It is a real measurement, at a lift no cooler has.

Inside a residential downdraft cooler the water climbs from the pan to the distributor above the pads. Champion's pads stand 27 to 36-1/4 in tall and its 3000, 4001 and 5000 DD cabinets are 33-7/16 to 42-7/16 in high, so the lift is roughly 2.5 to 3.5 ft before you count friction in the hose and spider. At 3 ft, the table shows Dial's concentric pumps keeping 85 to 91 percent of their box figure and Little Giant's CP series 86 to 91 percent, while Dial's offset pumps keep 73 to 85 percent. By 5 to 6 ft the losses spread out: Little Giant's CP3 keeps 82 percent at 5 ft, Dial's offset UL7000 just 32 percent at 6 ft. That matters on tall commercial cabinets.

Offset and concentric labels are not comparable

Here is the result nobody puts on the packaging. Dial's UL10000 is labeled for a 10,000 CFM cooler and its UL7500 for 7,500 CFM, yet the UL7500 moves more water at every height on Dial's chart: 360 against 290 GPH at 1 ft, 315 against 245 at 3 ft, and 205 against 130 at 6 ft. The difference is the design. The UL10000 is an offset pump; the UL7500 is concentric, which Dial describes as having heavy-duty bearings and pumping more water, more efficiently, than the offset design.

The CFM label is a sizing guide within one design line, not a ranking across them. Choosing between a "bigger" offset pump and a "smaller" concentric one, compare GPH at 3 ft.

How much water the pads actually need

The other side of the check is how much water the pads need to stay evenly wet, which depends on the length of pad the distributor feeds. University extension guides for fan-and-pad systems give the rates: Arkansas lists 0.30 gpm per linear foot for aspen, 0.50 for 4 in cellulose and 0.75 for 6 in cellulose; Connecticut gives 1/3 gpm per foot for aspen. Apply the aspen figures to Champion's pad widths from the pad size chart and you get a target for each cabinet.

Estimated aspen wetting flow for Champion residential coolers (0.30 to 0.33 gpm per foot of pad)
CoolerPad widthPad length fedFlow needed
3000 DD (4 pads)22 in7.3 ft130 to 145 GPH
4001 DD (4 pads)27-3/4 in9.25 ft165 to 185 GPH
5000 DD (4 pads)32-3/4 in10.9 ft195 to 220 GPH
3000 SD (3 pads)22 in5.5 ft100 to 110 GPH
4001 SD (3 pads)27-3/4 in6.9 ft125 to 140 GPH
5000 SD (3 pads)32-3/4 in8.2 ft145 to 165 GPH

Set against the 3 ft column above, the picture is clear. A 7,500 class concentric pump at about 315 GPH covers even the 5000 DD with room to spare. A 5,500 class pump at about 205 GPH covers the 3000 and 4001 easily but sits right at the line on a 5000 DD. Champion takes the simple route: its submittal sheet lists one pump, part 110436 at 120 V and 0.7 A, for every 3000, 4001 and 5000 cooler in both downdraft and side discharge, from 2,077 to 4,983 CFM. One residential pump class covers a wide band of coolers.

Worked example: replacing the pump on a 4001 DD

The cooler is a Champion 4001 DD with aspen pads. Four 27-3/4 in pads give 9.25 ft of pad top; at 0.30 to 0.33 gpm per foot that is 2.8 to 3.1 gpm, or 165 to 185 GPH. The lift is about 3 ft. A Dial UL7500 delivers about 315 GPH there, 70 to 90 percent more than the pads need, which is the margin you want as scale builds on the impeller. A UL5500 at about 205 GPH would also work, with less room for wear. Both are rated above the 4,900 CFM box figure.

If the pump is correctly sized and the pads still show dry streaks, the fault is usually downstream: a clogged spider, blocked trough holes or a kinked hose. The water distribution system guide covers those.

Rigid media, window and commercial coolers

MasterCool coolers ship with their pumps and an automatic dump system installed, per Champion's MasterCool submittal sheet. Dial's replacement for MasterCool units with 8 in and 12 in media is the MC8500UL (part 1442, 115 V) or MC8500-2UL (part 1443, 230 V), rated 4,000 to 8,500 CFM and 360 GPH. Single-inlet MasterCool, AeroCool, UltraCool and ComfortCool units use a different offset pump, Dial part 1438, rated 290 GPH for 8 in media. Dial's narrow profile pump, part 1148, is made for the MasterCool MCP44 window cooler and the Bonaire Durango, and Dial publishes no GPH for it. The extension rates above stop at 6 in cellulose, so they do not tell you what 8 or 12 in rigid media needs; follow the cooler maker's pump. More on these cabinets is in the MasterCool guide and aspen vs rigid media.

Commercial coolers above about 12,000 CFM move to industrial pumps: Dial's UL15000LA and UL25000LA, or Little Giant's CP3. These need a larger hose. Dial specifies 5/8 or 3/4 in inside diameter for both, and Little Giant specifies the same for the whole CP series, so a 1/2 in residential hose will throttle them. Larger installations are covered in the commercial cooling guide.

Voltage and current

Voltage has no effect on flow. Dial lists the same GPH for its 115 V and 230 V versions (UL7500 and UL7500-2 are both 360 GPH), and Little Giant prints identical curves for each pair. Current is small either way. Dial's contractor sheet lists 0.9, 1.2 and 1.7 A at 115 V for its three contractor pump sizes, and 0.5, 0.8 and 1.1 A at 230 V; Little Giant lists 0.8, 1.0 and 1.1 A at 115 V for the CP1 to CP3. Moving up a pump class barely changes the load on a circuit the breaker and wire size guide sizes around the blower motor.

Too big, too small, and the purge pump

An undersized pump leaves dry vertical streaks and warm corners on the pads, and the dry areas collect scale. An oversized one overflows the troughs and throws water through the pads into the blower. Step up one class at most; if the flow is still too strong, a hose restrictor clamp trims it. A pump also only delivers its rating if it never sucks air; Dial's troubleshooting guide sets the water about 1/2 in below the top of the overflow standpipe for that reason (your manual may differ; see float valve adjustment).

A purge pump is a separate, timed pump that empties the pan, and it is not sized to your cooler. Dial's Power Clean purge pump moves about 200 GPH in cycles of 7 to 8 minutes and empties a standard downdraft reservoir in 3 to 4 minutes. For how it compares with a bleed-off line, see bleed-off and water quality.

Where these numbers stop applying

The 3 ft and 6 ft Dial figures are read from a chart and are good to about 5 GPH. All flows are at 60 Hz and the rated voltage, with clean pumps; scale on the impeller and screen cuts them, which is why the margin matters. The pad wetting rates come from greenhouse fan-and-pad guidance, not from cabinet cooler makers, so treat them as a check on margin rather than a specification. Portable coolers use small model-specific pumps with no published curves; buy the maker's part. When you have the right size, how to replace a swamp cooler pump walks through the swap.

Frequently asked questions

How many GPH does a swamp cooler pump need?

A residential aspen cooler of 3,000 to 5,000 CFM needs roughly 130 to 220 GPH at the pads by university extension wetting rates. Replacement pumps for that size are rated 240 to 360 GPH at 1 ft of lift, which leaves margin for the 2.5 to 3.5 ft the water actually climbs.

Can I put a bigger pump in my swamp cooler?

One class up is usually fine if the troughs and distributor can carry the flow. Watch the first hour: water overflowing the troughs or spraying through the pads into the blower means the pump is too large or the hose needs a restrictor clamp.

Is a 10,000 CFM pump bigger than a 7,500 CFM pump?

Not always. Dial's UL10000 is an offset pump and its UL7500 is concentric. Dial's own chart shows the UL7500 moving more water at every lift height, so compare GPH within the same pump design, not the CFM label across designs.

Do 230 V cooler pumps pump more water than 115 V pumps?

No. Dial and Little Giant list the same GPH for the 115 V and 230 V versions of each pump. The 230 V version draws about half the current.

What size pump for a MasterCool rigid media cooler?

MasterCool coolers ship with their pumps installed. Dial's replacement for MasterCool units with 8 in and 12 in media is the MC8500UL (part 1442, 115 V) or MC8500-2UL (part 1443, 230 V), rated 4,000 to 8,500 CFM and 360 GPH.

Sources and further reading

  1. Pump Flow Rate Performance (120 VAC, 60 Hz): Dial Manufacturing Offset and Concentric Pumps, Dial Manufacturing
  2. Pump Flow Rate Performance: Dial Manufacturing UL 25000LA Pump, Dial Manufacturing
  3. Contractor Pumps Specifications (amps, horsepower, outlet sizes), Dial Manufacturing
  4. Pumps product catalog (UL5000 to UL25000LA, MC8500UL, single inlet and narrow profile pumps), Dial Manufacturing
  5. UL7500 Premium Pump (part 1175), Dial Manufacturing
  6. Frequently Asked Questions (Power Clean purge pump), Dial Manufacturing
  7. Troubleshooting Guide, Dial Manufacturing
  8. CP Series Evaporative Cooler Pump specifications, Franklin Electric, Little Giant
  9. LittleGIANT Cooler Pump 115Vac, 7,000 CFM, 307 GPH (CP1-115), Sigler
  10. Champion 3000, 4001 and 5000 DD/SD Specifications and Submittal Data (pump specifications, cabinet dimensions), Champion Cooler
  11. MasterCool AD/AS C51, C5112, C71 and C7112 Specifications and Submittal Data, Champion Cooler
  12. Fan and Pad Evaporative Cooling Systems (John W. Bartok, Jr.), University of Connecticut, Integrated Pest Management
  13. Greenhouse Management, Unit 6 Section 4: evaporative pad systems, University of Arkansas